HIGH-Z

Bus zone scheme

Three circuits on a 220 kV bus, Class PX CTs paralleled onto a high-impedance circulating-current zone. Shunt resistors turn spill current into voltage. 87BZ and the supervisory element measure that voltage.

Stable — no operate

Load current cancels

Infeeds and outfeeds sum to zero at the bus. Secondary currents circulate between CTs and almost none flows in the shunt resistors, so the voltage across them stays near zero.

Swipe the scheme to follow the wiring

High impedance bus zone scheme — Load current cancelsInfeeds and outfeeds sum to zero at the bus. Secondary currents circulate between CTs and almost none flows in the shunt resistors, so the voltage across them stays near zero.PRIMARY · 220 kV · PHASE A SHOWNFdr 1240 A inT1400 A outFdr 2160 A in220 kV BUSBARCT2000/1 PXCT2000/1 PXCT2000/1 PXCT SECONDARIES · PARALLELED ON THE BUS ZONES1S20.12 AS1S2-0.20 AS1S20.08 AP · BUS ZONE POLARITYN · BUS ZONE RESIDUALRstab2000 ΩMetrosilVDR clampRsup2000 ΩV0 VV0 VBUS ZONE DIFF87BZDiff0 Vset 150 VIDLESUPERVISORY87SCheck0 Vset 25 VIDLERelays measure voltage across the shunt resistors — they are high-impedance voltmeters, not current coils.Idiff = 0 A · V = Idiff × (Rstab ∥ Rsup)Class PX CTs · one point earthed on the residual bus · A, B, C are independent copies of this circuit

Differential current

0 A

Σ secondary (S1 sense)

Voltage across shunts

0 V

Idiff × 2000 Ω ∥ 2000 Ω

Relay states

Both idle

87BZ 150 V · 87S 25 V

Fdr 1
240 A pri · 0.12 A sec
T1
-400 A pri · -0.20 A sec
Fdr 2
160 A pri · 0.08 A sec
Shunt split
0 A Rstab · 0 A Rsup

PRINCIPLE

Why the secondaries are paralleled

Every circuit on the protected bus has a dedicated Class PX core, same ratio, P1 toward the bus. All S1 terminals land on one polarity bus; all S2 terminals land on one residual bus. Kirchhoff then does the comparison: any current that enters the bus must leave it, so the secondary currents cancel and nothing is left to push through the shunts.

Shunt resistors convert spill current to voltage

The paralleled secondaries are closed through two high-value resistors — Rstab for the bus-zone differential and Rsup for the supervisory. Spill current Idiff develops V = Idiff × (Rstab ∥ Rsup). 87BZ and 87S are voltage-operated elements measuring across those resistors. They are not series current coils.

Stability on a through fault

External fault current circulates around the CT secondaries and barely enters the high-impedance branch. Even if one CT saturates (its magnetising branch collapses toward a short), the healthy CTs still cannot force enough current through Rs to reach the 150 V setting. Typical rule of thumb: knee-point Vk ≥ 2 Vs, with Vs sized from Ifault (Rct + 2 Rl).

Internal fault and the Metrosil

On a bus fault every infeed adds. Idiff is large, the theoretical voltage is kilovolts, and the Metrosil (silicon-carbide VDR) conducts to clip the voltage so the CTs and wiring survive. Both relays see the clamped voltage and operate.

Supervisory element

87S is set well below 87BZ (25 V vs 150 V here). An open CT secondary, a high-resistance joint, or a wiring earth leaves a standing voltage from load current. Supervisory alarms without tripping the bus. Many HV boards also AND a check zone — a second high-Z circuit on a different core set — before issuing a trip.